-- Mitsubishi.mib - MIB file for Mitsubishi UPSs UPS-MIB DEFINITIONS ::= BEGIN IMPORTS TRAP-TYPE FROM RFC-1215 DisplayString FROM RFC1213-MIB OBJECT-TYPE FROM RFC-1212 Gauge, Counter, TimeTicks, mgmt FROM RFC1155-SMI ; PositiveInteger ::= INTEGER NonNegativeInteger ::= INTEGER TimeStamp ::= TimeTicks TimeInterval ::= INTEGER (0..2147483647) TestAndIncr ::= INTEGER (0..2147483647) AutonomousType ::= DisplayString Tag OBJECT IDENTIFIER ::= { enterprises 13891 } MitsubishiUPS OBJECT IDENTIFIER ::= { Tag 101 } upsIdent OBJECT IDENTIFIER ::= { MitsubishiUPS 1 } upsIdentManufacturer OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The name of the UPS manufacturer." ::= { upsIdent 1 } upsIdentModel OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The UPS Model designation." ::= { upsIdent 2 } upsIdentUPSSoftwareVersion OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations." ::= { upsIdent 3 } upsIdentAgentSoftwareVersion OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations." ::= { upsIdent 4 } upsIdentName OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A string identifying the UPS. This object should be set by the administrator." ::= { upsIdent 5 } upsIdentAttachedDevices OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "A string identifying the devices attached to the output of the UPS. This object should be set by the administrator." ::= { upsIdent 6 } upsBattery OBJECT IDENTIFIER ::= { MitsubishiUPS 2 } upsBatteryStatus OBJECT-TYPE SYNTAX INTEGER { unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4) } ACCESS read-only STATUS mandatory DESCRIPTION "The indication of the capacity remaining in the UPS batteries. A value of batteryNormal indicates a normal battery condition. A value of batteryLow indicates the remaining battery run-time will not maintain the output load for an extended period of time. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost." ::= { upsBattery 1 } upsSecondsOnBattery OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS seconds ACCESS read-only STATUS mandatory DESCRIPTION "If the unit is on battery power, the elapsed time in seconds since the UPS last switched to battery power, or the time since the network management system was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power." ::= { upsBattery 2 } upsEstimatedMinutesRemaining OBJECT-TYPE SYNTAX PositiveInteger -- UNITS minutes ACCESS read-only STATUS mandatory DESCRIPTION "An estimate of the time in minutes until the battery is depleted under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off." ::= { upsBattery 3 } upsEstimatedChargeRemaining OBJECT-TYPE SYNTAX INTEGER -- UNITS percent ACCESS read-only STATUS mandatory DESCRIPTION "An estimate of the battery charge remaining expressed as a percent of full charge." ::= { upsBattery 4 } upsBatteryVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Volt DC ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present battery voltage (0.1 Volt DC)." ::= { upsBattery 5 } upsBatteryCurrent OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) -- UNITS 0.1 Amp DC ACCESS read-only STATUS mandatory DESCRIPTION "The present battery current (0.1 Amp DC)." ::= { upsBattery 6 } upsBatteryTemperature OBJECT-TYPE SYNTAX INTEGER (-2147483648..2147483647) -- UNITS degrees Centigrade ACCESS read-only STATUS mandatory DESCRIPTION "The ambient temperature at or near the UPS Battery casing (degrees Centigrade)." ::= { upsBattery 7 } upsInput OBJECT IDENTIFIER ::= { MitsubishiUPS 3 } upsInputLineBads OBJECT-TYPE SYNTAX Counter ACCESS read-only STATUS mandatory DESCRIPTION "A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance." ::= { upsInput 1 } upsInputNumLines OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "The number of input lines utilized in this device. This variable indicates the number of rows in the input table." ::= { upsInput 2 } upsInputTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of input table entries. The number of entries is given by the value of upsInputNumLines." ::= { upsInput 3 } upsInputEntry OBJECT-TYPE SYNTAX UpsInputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular input line." INDEX { upsInputLineIndex } ::= { upsInputTable 1 } UpsInputEntry ::= SEQUENCE { upsInputLineIndex PositiveInteger, upsInputFrequency NonNegativeInteger, upsInputVoltage NonNegativeInteger, upsInputCurrent NonNegativeInteger, upsInputTruePower NonNegativeInteger } upsInputLineIndex OBJECT-TYPE SYNTAX PositiveInteger ACCESS read-only STATUS mandatory DESCRIPTION "The input line identifier." ::= { upsInputEntry 1 } upsInputFrequency OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The present input frequency (0.1 Hertz)." ::= { upsInputEntry 2 } upsInputVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Volt ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present input voltage (0.1 RMS Volt)." ::= { upsInputEntry 3 } upsInputCurrent OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present input current (0.1 RMS Amp)." ::= { upsInputEntry 4 } upsInputTruePower OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the present input true power (watts)." ::= { upsInputEntry 5 } upsOutput OBJECT IDENTIFIER ::= { MitsubishiUPS 4 } upsOutputSource OBJECT-TYPE SYNTAX INTEGER { other(1), none(2), normal(3), bypass(4), battery(5), booster(6), reducer(7) } ACCESS read-only STATUS mandatory DESCRIPTION "The present source of output power. A value of none (2) indicates there is no source of output power (and therefore no output power), for example, the system has opened the output breaker." ::= { upsOutput 1 } upsOutputFrequency OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The present output frequency (0.1 Hertz)." ::= { upsOutput 2 } upsOutputNumLines OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "The number of output lines utilized in this device. This variable indicates the number of rows in the output table." ::= { upsOutput 3 } upsOutputTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of output table entries. The number of entries is given by the value of upsOutputNumLines." ::= { upsOutput 4 } upsOutputEntry OBJECT-TYPE SYNTAX UpsOutputEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular output line." INDEX { upsOutputLineIndex } ::= { upsOutputTable 1 } UpsOutputEntry ::= SEQUENCE { upsOutputLineIndex PositiveInteger, upsOutputVoltage NonNegativeInteger, upsOutputCurrent NonNegativeInteger, upsOutputPower NonNegativeInteger, upsOutputPercentLoad INTEGER } upsOutputLineIndex OBJECT-TYPE SYNTAX PositiveInteger ACCESS read-only STATUS mandatory DESCRIPTION "The output line identifier." ::= { upsOutputEntry 1 } upsOutputVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The present output voltage (0.1 RMS Volt)." ::= { upsOutputEntry 2 } upsOutputCurrent OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp ACCESS read-only STATUS mandatory DESCRIPTION "The present output current (0.1 RMS Amp)." ::= { upsOutputEntry 3 } upsOutputPower OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The present output true power (watts)." ::= { upsOutputEntry 4 } upsOutputPercentLoad OBJECT-TYPE SYNTAX INTEGER -- UNITS percent ACCESS read-only STATUS mandatory DESCRIPTION "The percentage of the UPS power capacity presently being used on this output line (the greater of the percent load of true power capacity and the percent load of VA." ::= { upsOutputEntry 5 } upsBypass OBJECT IDENTIFIER ::= { MitsubishiUPS 5 } upsBypassFrequency OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz ACCESS read-only STATUS mandatory DESCRIPTION "The present bypass frequency." ::= { upsBypass 1 } upsBypassNumLines OBJECT-TYPE SYNTAX NonNegativeInteger ACCESS read-only STATUS mandatory DESCRIPTION "The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table." ::= { upsBypass 2 } upsBypassTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsBypassEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines." ::= { upsBypass 3 } upsBypassEntry OBJECT-TYPE SYNTAX UpsBypassEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular bypass input." INDEX { upsBypassLineIndex } ::= { upsBypassTable 1 } UpsBypassEntry ::= SEQUENCE { upsBypassLineIndex PositiveInteger, upsBypassVoltage NonNegativeInteger, upsBypassCurrent NonNegativeInteger, upsBypassPower NonNegativeInteger } upsBypassLineIndex OBJECT-TYPE SYNTAX PositiveInteger ACCESS read-only STATUS mandatory DESCRIPTION "The bypass line identifier." ::= { upsBypassEntry 1 } upsBypassVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Volts ACCESS read-only STATUS mandatory DESCRIPTION "The present bypass voltage (0.1 RMS Volt)." ::= { upsBypassEntry 2 } upsBypassCurrent OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp ACCESS read-only STATUS mandatory DESCRIPTION "The present bypass current (0.1 RMS Amp)." ::= { upsBypassEntry 3 } upsBypassPower OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The present true power conveyed by the bypass (watts)." ::= { upsBypassEntry 4 } upsAlarm OBJECT IDENTIFIER ::= { MitsubishiUPS 6 } upsAlarmsPresent OBJECT-TYPE SYNTAX Gauge ACCESS read-only STATUS mandatory DESCRIPTION "The present number of active alarm conditions." ::= { upsAlarm 1 } upsAlarmTable OBJECT-TYPE SYNTAX SEQUENCE OF UpsAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "A list of alarm table entries. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent." ::= { upsAlarm 2 } upsAlarmEntry OBJECT-TYPE SYNTAX UpsAlarmEntry ACCESS not-accessible STATUS mandatory DESCRIPTION "An entry containing information applicable to a particular alarm." INDEX { upsAlarmId } ::= { upsAlarmTable 1 } UpsAlarmEntry ::= SEQUENCE { upsAlarmId PositiveInteger, upsAlarmDescr AutonomousType, upsAlarmTime TimeStamp } upsAlarmId OBJECT-TYPE SYNTAX PositiveInteger ACCESS read-only STATUS mandatory DESCRIPTION "A unique identifier for an alarm condition. This value must remain constant." ::= { upsAlarmEntry 1 } upsAlarmDescr OBJECT-TYPE SYNTAX AutonomousType ACCESS read-only STATUS mandatory DESCRIPTION "A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition." ::= { upsAlarmEntry 2 } upsAlarmTime OBJECT-TYPE SYNTAX TimeStamp ACCESS read-only STATUS mandatory DESCRIPTION "The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0." ::= { upsAlarmEntry 3 } upsAlarmID OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A unique identifier for an alarm condition. This value must remain constant." ::= { upsAlarm 4 } upsAlarmDESCR OBJECT-TYPE SYNTAX DisplayString (SIZE(0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "A reference to an alarm description object. The object references should not be accessible, but rather be used to provide a unique description of the alarm condition." ::= { upsAlarm 5 } upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 3 } upsAlarmBatteryBad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "One or more batteries have been determined to require replacement." ::= { upsWellKnownAlarms 1 } upsAlarmOnBattery OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS is drawing power from the batteries." ::= { upsWellKnownAlarms 2 } upsAlarmLowBattery OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The remaining battery run-time is less than or equal to upsConfigLowBattTime." ::= { upsWellKnownAlarms 3 } upsAlarmDepletedBattery OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS will be unable to sustain the present load when and if the utility power is lost." ::= { upsWellKnownAlarms 4 } upsAlarmTempBad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A temperature is out of tolerance." ::= { upsWellKnownAlarms 5 } upsAlarmInputBad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "An input condition is out of tolerance." ::= { upsWellKnownAlarms 6 } upsAlarmOutputBad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "An output condition (other than OutputOverload) is out of tolerance." ::= { upsWellKnownAlarms 7 } upsAlarmOutputOverload OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output load exceeds the UPS output capacity." ::= { upsWellKnownAlarms 8 } upsAlarmOnBypass OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Bypass is presently engaged on the UPS." ::= { upsWellKnownAlarms 9 } upsAlarmBypassBad OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The Bypass is out of tolerance." ::= { upsWellKnownAlarms 10 } upsAlarmOutputOffAsRequested OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS has shut down as requested, i.e., the output is off." ::= { upsWellKnownAlarms 11 } upsAlarmUpsOffAsRequested OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The entire UPS has shutdown as commanded." ::= { upsWellKnownAlarms 12 } upsAlarmChargerFailed OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "An uncorrected problem has been detected within the UPS charger subsystem." ::= { upsWellKnownAlarms 13 } upsAlarmUpsOutputOff OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The output of the UPS is in the off state." ::= { upsWellKnownAlarms 14 } upsAlarmUpsSystemOff OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS system is in the off state." ::= { upsWellKnownAlarms 15 } upsAlarmFanFailure OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The failure of one or more fans in the UPS has been detected." ::= { upsWellKnownAlarms 16 } upsAlarmFuseFailure OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The failure of one or more fuses has been detected." ::= { upsWellKnownAlarms 17 } upsAlarmGeneralFault OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A general fault in the UPS has been detected." ::= { upsWellKnownAlarms 18 } upsAlarmDiagnosticTestFailed OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The result of the last diagnostic test indicates a failure." ::= { upsWellKnownAlarms 19 } upsAlarmCommunicationsLost OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A problem has been encountered in the communications between the agent and the UPS." ::= { upsWellKnownAlarms 20 } upsAlarmAwaitingPower OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS output is off and the UPS is awaiting the return of input power." ::= { upsWellKnownAlarms 21 } upsAlarmShutdownPending OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A upsShutdownAfterDelay countdown is underway." ::= { upsWellKnownAlarms 22 } upsAlarmShutdownImminent OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown." ::= { upsWellKnownAlarms 23 } upsAlarmTestInProgress OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-TYPE macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-TYPE." ::= { upsWellKnownAlarms 24 } upsTest OBJECT IDENTIFIER ::= { MitsubishiUPS 7 } upsTestId OBJECT-TYPE SYNTAX OBJECT IDENTIFIER ACCESS read-write STATUS mandatory DESCRIPTION "The test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of a test, including the well known tests identified in this document." ::= { upsTest 1 } upsTestSpinLock OBJECT-TYPE SYNTAX TestAndIncr ACCESS read-write STATUS mandatory DESCRIPTION "A spin lock on the test subsystem." ::= { upsTest 2 } upsTestResultsSummary OBJECT-TYPE SYNTAX INTEGER { donePass(1), doneWarning(2), doneError(3), aborted(4), inProgress(5), noTestsInitiated(6) } ACCESS read-only STATUS mandatory DESCRIPTION "The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results." ::= { upsTest 3 } upsTestResultsDetail OBJECT-TYPE SYNTAX DisplayString ACCESS read-only STATUS mandatory DESCRIPTION "Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned." ::= { upsTest 4 } upsTestStartTime OBJECT-TYPE SYNTAX TimeStamp ACCESS read-only STATUS mandatory DESCRIPTION "The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0." ::= { upsTest 5 } upsTestElapsedTime OBJECT-TYPE SYNTAX TimeInterval ACCESS read-only STATUS mandatory DESCRIPTION "The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0." ::= { upsTest 6 } upsWellKnownTests OBJECT IDENTIFIER ::= { upsTest 7 } upsTestNoTestsInitiated OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "No tests have been initiated and no test is in progress." ::= { upsWellKnownTests 1 } upsTestAbortTestInProgress OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The test in progress is to be aborted / the test in progress was aborted." ::= { upsWellKnownTests 2 } upsTestGeneralSystemsTest OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The manufacturer's standard test of UPS device systems." ::= { upsWellKnownTests 3 } upsTestQuickBatteryTest OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "A test that is sufficient to determine if the battery needs replacement." ::= { upsWellKnownTests 4 } upsTestDeepBatteryCalibration OBJECT-TYPE SYNTAX INTEGER ACCESS read-only STATUS mandatory DESCRIPTION "The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load." ::= { upsWellKnownTests 5 } upsControl OBJECT IDENTIFIER ::= { MitsubishiUPS 8 } upsShutdownType OBJECT-TYPE SYNTAX INTEGER { output(1), system(2) } ACCESS read-write STATUS mandatory DESCRIPTION "This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off." ::= { upsControl 1 } upsShutdownAfterDelay OBJECT-TYPE SYNTAX INTEGER -- UNITS seconds ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect." ::= { upsControl 2 } upsStartupAfterDelay OBJECT-TYPE SYNTAX INTEGER -- UNITS seconds ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted." ::= { upsControl 3 } upsRebootWithDuration OBJECT-TYPE SYNTAX INTEGER -- UNITS seconds ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored." ::= { upsControl 4 } upsAutoRestart OBJECT-TYPE SYNTAX INTEGER { on(1), off(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied." ::= { upsControl 5 } upsConfig OBJECT IDENTIFIER ::= { MitsubishiUPS 9 } upsConfigInputVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS RMS Volts ACCESS read-write STATUS mandatory DESCRIPTION "The magnitude of the nominal input voltage (RMS Volts). On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2." ::= { upsConfig 1 } upsConfigInputFreq OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz ACCESS read-write STATUS mandatory DESCRIPTION "The nominal input frequency (0.1 Hertz). On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2." ::= { upsConfig 2 } upsConfigOutputVoltage OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS RMS Volts ACCESS read-write STATUS mandatory DESCRIPTION "The magnitude of the nominal output voltage (RMS Volts). On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2." ::= { upsConfig 3 } upsConfigOutputFreq OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz ACCESS read-write STATUS mandatory DESCRIPTION "The nominal output frequency (0.1 Hertz). On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2." ::= { upsConfig 4 } upsConfigOutputVA OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS Volt-Amps ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the nominal Volt-Amp rating (Volt-Amps)." ::= { upsConfig 5 } upsConfigOutputPower OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS Watts ACCESS read-only STATUS mandatory DESCRIPTION "The magnitude of the nominal true power rating (watts)." ::= { upsConfig 6 } upsConfigLowBattTime OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS minutes ACCESS read-write STATUS mandatory DESCRIPTION "The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected." ::= { upsConfig 7 } upsConfigAudibleStatus OBJECT-TYPE SYNTAX INTEGER { disabled(1), enabled(2), muted(3) } ACCESS read-write STATUS mandatory DESCRIPTION "The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect." ::= { upsConfig 8 } upsConfigLowVoltageTransferPoint OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS RMS Volts ACCESS read-write STATUS mandatory DESCRIPTION "The minimum input line voltage (RMS Volts) allowed before the UPS system transfers to battery backup." ::= { upsConfig 9 } upsConfigHighVoltageTransferPoint OBJECT-TYPE SYNTAX NonNegativeInteger -- UNITS RMS Volts ACCESS read-write STATUS mandatory DESCRIPTION "The maximum line voltage (RMS Volts) allowed before the UPS system transfers to battery backup." ::= { upsConfig 10 } -- UPS trap information group upsTrapInfo OBJECT IDENTIFIER ::= { MitsubishiUPS 10 } trapCode OBJECT-TYPE SYNTAX Unsigned32 ACCESS read-only STATUS mandatory DESCRIPTION "A number identifying the event for that last trap that was sent." ::= { upsTrapInfo 1 } trapDescription OBJECT-TYPE SYNTAX DisplayString (SIZE (0..63)) ACCESS read-only STATUS mandatory DESCRIPTION "A string identifying the event for that last trap that was sent." ::= { upsTrapInfo 2 } -- UPS Traps -- upsTraps OBJECT IDENTIFIER ::= { Tag 101 } alarmCritical TRAP-TYPE ENTERPRISE MitsubishiUPS VARIABLES { trapCode, trapDescription } DESCRIPTION "Critical alarm." ::= 1 alarmWarning TRAP-TYPE ENTERPRISE MitsubishiUPS VARIABLES { trapCode, trapDescription } DESCRIPTION "Warning alarm." ::= 2 alarmInformation TRAP-TYPE ENTERPRISE MitsubishiUPS VARIABLES { trapCode, trapDescription } DESCRIPTION "Information alarm." ::= 3 upsAlarmCleared TRAP-TYPE ENTERPRISE MitsubishiUPS VARIABLES { trapCode, trapDescription } DESCRIPTION "Alarm cleared." ::= 4 upsTrapInitialization TRAP-TYPE ENTERPRISE MitsubishiUPS VARIABLES { upsIdentName } DESCRIPTION "This trap is sent each time a NetCom device is initialized." ::= 5 END